Add to Cart
Construction:
· Frame: High quality extruded aluminum alloy(A6063) profile with 30mm flange as standard.
· Blades: Aerofoil blades in 45° from aluminum profile
· Blades spacing: 35mm as standard
· Support pipe: 8mm diameter aluminum pipe
Description:
· Fresh air louver is composed of frame and horizontal blades assembly, manufactured from high quality extruded aluminum profiled construction with advantages of corrosion resistance and rigidity.
· Blades are set at angle of 45° with 30mm spacing, and fixed to the inner frame by rivets and support pipe.
· Total structure is weather proofed and blades are inclined down wards to protect against rain water.
· Structure provides around 45% effective pressure area .
Surface Finish:
· Powder coated color finish as per RAL color----standard color: RAL9016, 9010
· Natural anodized aluminum finish
1), double adjustable blade, can get different air supply distance and different diffusion angle
2), can be used as air outlet
3), optional aluminum or iron production
4), can be used with the regulating valve
1).Widely used in air conditioning system as air outlet, according to the requirements, the air outlet can be prepared behind the aluminum air flow control valve (Hue word gate), double louver air outlet with two layers of vertical pages to adjust the horizontal and vertical page angle, adjust Air diffuser surface, to change the range, the air outlet frame width has two kinds of wide frame and narrow frame, can be used for special requirements of the ventilation system.
2). Usually installed on the pipe or side wall as a side air outlet. The double louver air outlet has two movable blades with adjustable angle. The short blades are used to adjust the spread angle of the air supply air, and can also be used to change the direction of air flow; The blades can make the supply air flow attached to the ceiling or tilt down at a certain angle (when heating the air). The outer blades of a double shutter air outlet or the blades of a single louver air outlet can be parallel to the long side or parallel to the short side , can choose according to the customer's request.
Size(mm) | 100x100 | 100x150 | 100x200 150x150 |
100x250 | 100x100 | 100x100 | |||||||||||
The wind speed of neck m/s |
Angle of blow | Air supply | Air return |
· Air Volume m/h |
Reach the distance m |
· Air flow m/h |
Reach the distance m |
· Air flow m/h |
Reach the distance m |
· Air flow m/h |
Reach the distance m |
· Air flow m/h |
Reach the distance m |
· Air flow m/h |
Reach the distance m | ||
· total pressure loss |
· static pressure loss |
· total pressure loss |
· static pressure loss | ||||||||||||||
1 | A B C D |
0.11 0.17 0.21 0.28 |
0.05 0.11 0.15 0.22 |
0.07 | 0.13 | 36 | 1.05 0.87 0.67 0.42 |
55 | 1.28 1.06 0.81 0.51 |
70 | 1.49 1.23 0.94 0.59 |
90 | 1.66 1.37 1.05 0.64 |
110 | 1.81 1.50 1.15 0.72 |
125 | 1.96 1.62 1.24 0.78 |
2 | A B C D |
0.44 0.67 0.85 1.11 |
0.20 0.43 0.61 0.87 |
0.29 | 0.54 | 72 | 1.77 1.47 1.20 0.72 |
110 | 2.17 1.79 1.46 0.88 |
140 | 2.51 2.08 1.70 1.02 |
180 | 2.79 2.30 1.89 1.14 |
220 | 3.06 2.54 2.07 1.25 |
250 | 3.31 2.74 2.24 1.35 |
3 | A B C D |
0.99 1.52 1.90 2.49 |
0.44 0.97 1.35 1.94 |
0.67 | 1.22 | 1.08 | 2.34 1.86 1.60 0.98 |
165 | 2.86 2.28 1.96 1.20 |
210 | 3.31 2.64 2.27 1.39 |
270 | 3.68 2.94 2.53 1.55 |
330 | 4.04 3.22 2.77 1.70 |
375 | 4.37 3.48 3.00 1.84 |
4 | A B C D |
1.76 2.70 3.38 4.43 |
0.78 1.72 2.40 3.45 |
1.18 | 2.16 | 1.44 | 2.69 2.20 1.83 0.18 |
220 | 3.28 2.69 2.24 1.44 |
280 | 3.81 3.12 2.59 1.66 |
360 | 4.26 3.47 2.88 1.85 |
440 | 4.46 3.80 3.16 2.03 |
500 | 5.02 4.11 3.42 2.19 |
5 | A B C D |
2.75 4.21 5.28 6.92 |
1.22 2.68 3.75 5.39 |
1.85 | 3.38 | 1.80 | 2.94 2.54 2.03 1.33 |
275 | 3.59 3.11 2.48 1.63 |
350 | 4.16 3.60 2.88 1.89 |
450 | 4.63 4.01 3.20 2.10 |
550 | 5.07 4.39 3.51 2.30 |
625 | 5.49 4.75 3.80 2.49 |