Add to Cart
The device used in the clean room of the pharmaceutical industry is below the high-efficiency filter at the air outlet. The use of the equalizing membrane is generally seen in the 10,000, 1000 and 100 clean rooms of the pharmaceutical industry when the requirements for cleanliness are relatively high. The filtering effect of the membrane itself is not very strong, and the dust filtering is mainly controlled by the front high efficiency filter. The function of the equalizing membrane is mainly embodied in the word “average flow”, which means literally. The airflow from the high-efficiency filter of the air outlet is evenly laminated down without turbulent flow, so that the cleanliness can be better controlled to achieve the effects of 10,000, 1000 and 100.
Usually its style is more rectangular, of course, this can be customized according to the size. The outer frame material is generally aluminum alloy and stainless steel.
1. Overview
It plays a role in the vertical passage of the airflow and changes the turbulent flow of the original airflow. The deviation between the point-by-point wind speed and the average wind speed can be within ±10%.
Adopting a uniform flow film to minimize the exposure of parts, easy to clean, beautiful and generous
2.Characteristics
Main features of the equalizing film: high light transmission, breathable (small wind resistance), waterproof, easy to clean, acid and alkali resistant.
Continuous stable operating temperature: no higher than 70℃
3.Technical parameters.
Aluminum bracket, specifications are 18*22mm, 15*25mm, 20*30mm, 25*38mm, 35*50mm (X type), etc., wall thickness 1.2-2.0mm.
304# stainless steel bracket, specifications are 13*25mm, 15*15mm, 15*30mm, 19*19mm, 25*38mm, 25*50mm, wall thickness 1.5-2.0mm.
The average film size ranges from 50 mesh to 500 mesh
4. Application:
purification equipment, weighing room, transfer window, purification workbench, clean room ceiling, pharmaceutical factory.
Customizable any non-standard size
Size(mm) | 100x100 | 100x150 | 100x200 150x150 | 100x250 | 100x100 | 100x100 | |||||||||||
The wind speed of neck m/s | Angle of blow | Air supply | Air return | · Air Volume m/h | Reach the distance m | · Air flow m/h | Reach the distance m | · Air flow m/h | Reach the distance m | · Air flow m/h | Reach the distance m | · Air flow m/h | Reach the distance m | · Air flow m/h | Reach the distance m | ||
· total pressure loss | · static pressure loss | · total pressure loss | · static pressure loss | ||||||||||||||
1 | A B C D | 0.11 0.17 0.21 0.28 | 0.05 0.11 0.15 0.22 | 0.07 | 0.13 | 36 | 1.05 0.87 0.67 0.42 | 55 | 1.28 1.06 0.81 0.51 | 70 | 1.49 1.23 0.94 0.59 | 90 | 1.66 1.37 1.05 0.64 | 110 | 1.81 1.50 1.15 0.72 | 125 | 1.96 1.62 1.24 0.78 |
2 | A B C D | 0.44 0.67 0.85 1.11 | 0.20 0.43 0.61 0.87 | 0.29 | 0.54 | 72 | 1.77 1.47 1.20 0.72 | 110 | 2.17 1.79 1.46 0.88 | 140 | 2.51 2.08 1.70 1.02 | 180 | 2.79 2.30 1.89 1.14 | 220 | 3.06 2.54 2.07 1.25 | 250 | 3.31 2.74 2.24 1.35 |
3 | A B C D | 0.99 1.52 1.90 2.49 | 0.44 0.97 1.35 1.94 | 0.67 | 1.22 | 1.08 | 2.34 1.86 1.60 0.98 | 165 | 2.86 2.28 1.96 1.20 | 210 | 3.31 2.64 2.27 1.39 | 270 | 3.68 2.94 2.53 1.55 | 330 | 4.04 3.22 2.77 1.70 | 375 | 4.37 3.48 3.00 1.84 |
4 | A B C D | 1.76 2.70 3.38 4.43 | 0.78 1.72 2.40 3.45 | 1.18 | 2.16 | 1.44 | 2.69 2.20 1.83 0.18 | 220 | 3.28 2.69 2.24 1.44 | 280 | 3.81 3.12 2.59 1.66 | 360 | 4.26 3.47 2.88 1.85 | 440 | 4.46 3.80 3.16 2.03 | 500 | 5.02 4.11 3.42 2.19 |
5 | A B C D | 2.75 4.21 5.28 6.92 | 1.22 2.68 3.75 5.39 | 1.85 | 3.38 | 1.80 | 2.94 2.54 2.03 1.33 | 275 | 3.59 3.11 2.48 1.63 | 350 | 4.16 3.60 2.88 1.89 | 450 | 4.63 4.01 3.20 2.10 | 550 | 5.07 4.39 3.51 2.30 | 625 | 5.49 4.75 3.80 2.49 |